ST-16-018 — A Simulation-Based Study on Different Control Strategies for Variable-Speed Pumps in Distributed Ground-Source Heat Pump Systems

$7.50

Conference Proceeding by ASHRAE, 2016

Category:

Description

Most commercial ground-source heat pump (GSHP) systems in the United States are in a distributed configuration. These systems circulate water or an anti-freeze solution through multiple heat pump units via a central pumping system, which usually uses variable-speed pumps. Variable speed pumps have potential to significantly reduce pumping energy use; however, the energy savings in reality could be far lower than its potential due to improper pumping system design and controls. In this paper, a simplified hydronic pumping system was simulated with the dynamic Modelica models to evaluate three different pumping control strategies. The pumping control strategies include two conventional control strategies: one strategy is to maintain a constant differential pressure across either the supply and return mains and the other is to maintain a constant differential pressure at the most hydraulically remote heat pump. There is also an innovative control strategy that adjusts system flow rate based on the demand of each heat pump. The simulation results indicate that a significant overflow occurs at part-load conditions when the variable-speed pump is controlled to maintain a constant differential pressure across the supply and return mains of the piping system. On the other hand, an underflow occurs at part-load conditions when the variable-speed pump is controlled to maintain a constant differential pressure across the furthest heat pump. The flow-demand-based control can provide needed flow rate to each heat pump at any given time and with less pumping energy use than the two conventional controls. Finally, a typical distributed GSHP system was studied to evaluate the energy saving potential of applying the flow-demand-based pumping control strategy.

This case study shows that the annual pumping energy consumption can be reduced by 64% using the flow-demand-based control compared withusing the conventional pressure based control to maintain a constant differential pressure across the supply and return mains.

Citation: 2016 Annual Conference, St. Louis, MO, Transactions 2016, Vol 122 pt. 2

Product Details

Published:
2016
Number of Pages:
13
Units of Measure:
Dual
File Size:
1 file , 7 MB
Product Code(s):
D-ST-16-018