Sale!

4301 (RP-824) — Measurement of Frost Characteristics on Heat Exchanger Fins Part I: Test Facility and Instrumentation

$7.50

Conference Proceeding by ASHRAE, 1999

Category:

Description

A special test facility was developed to characterize frost growing on heat exchanger fins where the cold surfaces and the air supply conditions were similar to those experienced in freezers, i.e., cold surface temperatures ranging from -35°C to -40°C (-31°F to -40°F), air supply temperatures from -10°C to -20°C (14°F to -4°F), and 80% to 100% relative humidity (RH). This test facility included a test section with removable fins to measure the frost height and mass concentration. Frost height on heat exchanger fins was measured using a new automated laser scanning system to measure the height of frost and its distribution on selected fins. The increase in air pressure loss resulting from frost growth on the fins was measured directly in the test loop. The frost mass accumulation distribution was measured for each test using special pre-etched fins that could be easily subdivided and weighed. The total heat rate was measured using a heat flux meter. These frost-measuring instruments were calibrated and the uncertainty of each is stated.

Units: Dual

Citation: ASHRAE Transactions, vol. 105, pt. 2

Product Details

Published:
1999
Number of Pages:
11
File Size:
1 file , 1.4 MB
Product Code(s):
D-7419