Description
Provides a performance investigation of rotary compressors with five kinds of lubricants. Experiments on 19 test-working conditions, including the standard working condition (condensing temperature 54.4degC [129.9degF], evaporating temperature -23.3degC [-10degF]) for each lubricant, were conducted. The results of the experiments showed that coefficient of performance (COP) for HFC134a is lower than that for CFC12 when the evaporating temperature is below -20degC (-4degF). When the evaporating temperature is over -20degC (-4degF), the opposite results are obtained.
KEYWORDS: year 1995, experiment, comparing, performance, rotary compressors, compressors, lubricants, R134a, replacing, R134, R12, refrigerants, coefficient of performance
Citation: ASHRAE Trans. 1995, Vol.101, Part 2, Paper number 3908, 335-340 7 figs., 3 tabs., 3 refs.
Product Details
- Published:
- 1995
- File Size:
- 1 file , 440 KB
- Product Code(s):
- D-16926