Description
Describes a laboratory study to evaluate the capability of curtain fire dampers and multiblade fire/smoke dampers to close at air velocities and closure pressures at the ambient and elevated temperatures that may occur in smoke management systems. All dampers were UL 555 dynamically rated for closure. Most of the curtain fire dampers did not close properly at their labelled dynamic UL rating and, at elevated temperatures, the closure failure rate increased significantly. Most of the multiblade fire/smoke dampers closed at their labelled dynamic UL rating at 70degF as well as at temperatures up to 450degF. Gives the result of tests of the leakage of multiblade fire/smoke dampers at elevated temperatures after dynamic closure.
KEYWORDS: year 1995, Laboratory testing, fire dampers, multileaf fire dampers, reliability, leaking
Citation: ASHRAE Trans. 1995, Vol.101, Part 2, Paper number 3906 (RP-680), 302-321, 14 figs, 7 tabs.
Product Details
- Published:
- 1995
- File Size:
- 1 file , 1.9 MB
- Product Code(s):
- D-16924