Description
A coriolis effect mass flow meter was tested under conditions of single-and two-phase refrigerant (R-22) flow to determine the effect of refrigerant quality on the accuracy of the meter. The meter was found to perform well for single-phase flow measurement, but measuring accuracy decreased drastically with the addition of a second phase. For the particular meter and flow rate tested, refrigerant vapor mass fractions from 1 to 72% produced a zero flow indication. The ability of a turbine flowmeter to measure liquid refrigerant mass flow rate in conventional refrigerating cycle systems was also examined.
Citation: ASHRAE Transactions, 1985, vol. 91, pt. 1A, Chicago, IL
Product Details
- Published:
- 1985
- Number of Pages:
- 12
- File Size:
- 1 file , 970 KB
- Product Code(s):
- D-CH-85-2878